ALPHA-VISION® History: AV AbvSpu |
| CardId | Description |
|---|---|
| 5942 |
[CopyOf:5938]AbvSpu (SAPI/MsPo version): If the status changes to FADED_OUT the alarm level is set to 0.
*Released as SpuOpt_v259a.zip and SpuOpt_V260b.zip *SpuOpt_V260a.zip contained an error in SpuOpt_Sapi_1.awl |
| CardId | Description |
|---|---|
| 5938 |
AbvSpu (SAPI/MsPo version): If the status changes to FADED_OUT the alarm level is set to 0.
*Released as SpuOpt_v259a.zip and SpuOpt_V260b.zip *SpuOpt_V260a.zip contained an error in SpuOpt_Sapi_1.awl |
| CardId | Description |
|---|---|
| 5749 | AvET, AbvSpu-generation: in DB189 (dynamic limits), field CnvGrp contains a scaling group number but with an offset of +1 |
| 5883 | AbvSpu: If during the calculation of dynamic limits a newly calculated limit changes rapidly and overlaps with a limit from the last cycle the new value is considered invalid and the limit will not be changed |
| CardId | Description |
|---|---|
| 5806 | AbvSpu (MpPv): Sending hysteresis is not correctly evaluated in FC 111 (value), FC 113 (dynamic limits) |
| 5748 | AvET, AbvSpu-generation: in DB188 scaling groups are generated in wrong order because the scaling group numbers are sorted as strings. All scaling groups starting with digit "1" are sorted before scaling groups starting with digit "2", e.g. "10" < "2". |
| CardId | Description |
|---|---|
| 5698 |
Integration of AbvSpu into AV-Siemens installer, AbvSpu version is now equal to the AlphaVision version. AbvSpu is installed
as max. 3 zip-files in the extinst directory. Installation description in install.txt updated.
* Checking AVLean installs the UDP variant for measuring points and process variables * Checking AVSapi installs the SAPI variants for measuring points and process variables and process objects |
| CardId | Description |
|---|---|
| 4968 |
AbvSpu - UDP-version evaluates DB 195 at address 162 (Number of PCs) and does nothing if the number of PCs is zero. This
setting is only valid for the Sapi-version, where the number of PCs is important. The UDP-version uses broadcast / multicast
and is independent of the number of PCs.
----- Workaround: Set the number of PCs to 1 using the Sapi-settings in AvET. |
| CardId | Description |
|---|---|
| 5078 | Im FC 191 wird die "TotalPacketLength" eines empfangenen Telegramms an mehreren Stellen mit "TAD" bearbeitet. Dadurch stimmt die Länge des Telegramms nicht mit der Datenlänge überein, es ist keine Kommunikation möglich. |