ALPHA-VISION® Info: Alarmgroups
|
Alarmgroups
SUMMARY
DataObjects of the type ‘Mp’ and ‘PV’ may be arranged in AlarmGroups.
CONTENTS
- Introduction
- Create GroupAlarmLists
- Delete/ Modify/ Create/ Groupalarms
- Properties
Introduction
DataObjects of the type ‘Mp’ and ‘PV’ may be arranged in AlarmGroups.
To an AlarmGroup two alarm counter objects can be allocated by selection;
these DataObjects keep the number of actual alarms (acknowledged –
unacknowledged) as value.
The status of these Dataobjects keeps the following information:
- Status 0 - no Groupalarm
- Status 1 - min. 1 Groupalarm
- Status 2 - min. 1 Groupalarm unacknowledged
A DataObject may belong to ONE AlarmGroup only.
Note:
If the alarm counter should be available on the SPS no ‘SO’ must be defined
since properties of these DataObjects are not transmitted to the SPS.
In the AvET:
- GroupAlarms are combined in GroupAlarmLists.
- GroupAlarmLists got the extension ".agr.xml"
Using the AvET you may:
- Create GroupAlarmLists.
- Import GroupAlarms.
- Export GroupAlarms.
- Create GroupAlarms within GroupAlarmLists.
- Modify GroupAlarms within GroupAlarmLists.
- Delete GroupAlarms within GroupAlarmLists.
Create GroupAlarmLists
Recommendation:
Create a subfolder called "GroupAlarm" in the Project folder.
In the pull down menu ‘File’ of the toolbar - select "new".
In the opened window select the item “GroupAlarmList”.
Input the wanted name in the ‘Name’ –field and the wanted location below.
Note:
The path of the opened project is shown, it may be extended - not
existent directories are created.
Finish with OK.
Note:
A GroupAlarmList with the given name and the extension ".agr.xml" is
created in the defined folder and shown in the tree in the left window.
Information about entries in the fields you will find down below under
the headline ‘properties’.
Delete/ Modify/ Create/ Groupalarms
Open the wanted GroupAlarmList via double-click.
- In the center window the GroupAlarms of the GroupAlarmList are
shown.
- The right window shows the properties of the Group-Alarm-List
itself.
In the toolbar are the actions ‘apply’, ‘reset’ and ‘new Object’ operable.
Delete GroupAlarm
Select the wanted GroupAlarm in the center window.
- The right window shows the definitions for that Groupalarm.
- The 'delete' symbol in the toolbar becomes operable.
Click the 'delete' symbol in the toolbar.
- In the center window the entry is deleted.
- The right window is empty.
If on closing the file the modification is confirmed, the deletion is
final.
Modify GroupAlarm
Select the wanted GroupAlarm in the center window.
- The right window shows the definitions for that Groupalarm.
In the right window you may modify the definitions.
- The field name of a modified field is marked with an asterisk.
- If the symbol ‘Apply’ is clicked the asterisk disappears.
If on closing the file the modification is confirmed, the change is
final.
Information about entries in the fields you will find down below under
the headline ‘properties’.
Create GroupAlarm
Select ‘New Object’ in the toolbar.
A GroupAlarm is created.
- The system places the default name AGrN (N stands for the running
number)
If on closing the file the modification is confirmed, the newly
created GroupAlarm is saved.
Information about entries in the fields you will find below under
the headline ‘properties’.
Properties
| List name: |
Group-Alarm-List |
| File extension: |
.agr.xml |
| Objects: |
GroupAlarm |
Properties of the Group-Alarm-List
| Field (Name in Refresh- Actionscript & XML-Files) |
Description |
assosiated VisuNT-Field (max.Lenght) |
| Name (Name) |
Name of the Group-Alarm-List |
non-existent |
| Description |
free Text |
non-existent |
Properties of Alarmgroups
| Field (Name in Refresh- Actionscript & XML-File) |
Description |
assosiated VisuNT-Field (max.Lenght) |
| Name (Name) |
Name of the Alarmgroup |
_grpalarm.dbf: grpalarm (5) |
| Description |
free Text |
_grpalarm.dbf: descr (30) |
| AlarmCounterObject |
DataObject, that holds the number
of alarms for that group.
|
_grpalarm.dbf: pntid (22) |
| AlarmCounterObject (unacknowledged) |
DataObjekt, that holds the number
of unacknowledged alarms for that group.
|
_grpalarm.dbf: pntiduack (22) |