ALPHA-VISION® Info: Measuringpoints |
Measuring Points may be combined in Lists with other DataObjects. There are
two types of MPs: analog and binary.
The _MP .dbf tables in Vision NT are different to that in AvET, they deviate
in Event-Registration :
The Status definitions assigned to a MP are edited in a separate window below
the DataObject List.
| List name: | DataObjektList |
| File extension: | .obj.xml |
| Objects: | ana.MP - bin.MP |
| Field (Name in Refresh- Aktionskript & XML-Files) | Description | Appropriate VisuNT-Field (max.Lenght) |
|---|---|---|
| Name (Name) | Name of the DataObjektList | not available |
| Description (Descr) | free Text | not available |
| UserDefinedClass (UserDefinedClass) | not relevant for Export- and AWL-Functionality | not available |
| Field (Name in Refresh- Aktionskript & XML-Files) | Description | Appropriate VisuNT-Field (max.Lenght) |
|---|---|---|
| Name (Name) | Name of the MP | _mp.dbf: pointid (22) |
| Description (Descr) | free Text | _mp.dbf: descript (30) |
| Station (Station) | Name of the Station the Mp belongs to | _mp.dbf: station (32) |
| objekt number (ObjNum) | Objektnumber of the MP, not editable, it is generated automatically for all DataObjects by the program when generating Objectnumbers | _mp.dbf: objid (10) |
| help-ID | Help-ID | _mp.dbf: hiti (6) |
| Alarmdisplay (AIPI) | Name of the attached AlarmPicture | _mp.dbf: aipi (6) |
| Process connection (IoAdr) | I/O-Signal address in the station | _mp.dbf: ioadr (32) |
| Groupalarm (GrpAlarm) | ID of the assigned AlarmGroup | _mp.dbf: grpalarm (5) |
| Technologygroup (TechGrp) | ID of the assigned TechnologyGroup | _mp.dbf: tid (2) |
| Event registration (EvenrReg) | Entry to the archive: no / Archiv / Print; Print includes Archiv | Not available: Summing up of _mp.dbf: evl1 - evl8 and evp1 - evp8 |
| Initialvalue (InitValue) | Value for initialising the MP | _mp.dbf: initval (9) |
| Using Initialvalue (InitValueFlag) | MP initialising: yes / no | _mp.dbf: initvalflg (1) |
| Valueformat (ValueFormat) | ValueFormat: float / unsigned / signed / timer / BCD | _mp.dbf: vf (1) |
| Scancycle (ScanCycle) | is not interpreted | _mp.dbf: scancycle (2) |
| Accessright acknowledge (AcknAccessRight) | Id for Access Right to acknowledge alarms | _mp.dbf: ackngp (3) |
| Accessright parameterchange (ParamAccessRight) | Id for Access Right to change Parameters | _mp.dbf: chgpgr (3) |
| Link (Link) | ? | _mp.dbf: link (32) |
| Transmitter (Transmitter) | Name of a Transmitters, analog MPs only | _mp.dbf: ifadr (13) |
| Slot (Slot) | ? | _mp.dbf: slot (30) |
| SpltId (SpltId) | ? | _mp.dbf: spltid (6) |
| Remark (Remark) | free Text | _mp.dbf: remark (20) |
| Alarmvideo (Alvi) | Alarmvideo | _mp.dbf: aivi (6) |
| Undefined-Group (UndefGrp) | for AbvSpu: not interpreted yet | _mp.dbf: undefgr (3) |
| Commentary (Comment) | free Text | _mp.dbf: comment (14) |
| Unit (UnitMls) | analog MPs only: Name of the String that points to the Unit | _mp.dbf: unit (32) |
| Measuring Range begin (RangeStartPlc) | analog MPs only: Range Start of a MP | _mp.dbf: rangestart (9) |
| Measuring Range end (RangeEndPlc) | analog MPs only: Range End of a MP | _mp.dbf: rangeend (9) |
| Send hysteresis (SendDeadband) | analog MPs only: Delay on triggering an event | _mp.dbf: sndhys (9) |
| Limit hysteresis (LimitDeadband) | analog MPs only: Delay on exceeding a limit | _mp.dbf: lmthys (9) |
| Filterfactor (SmoothFactor) | analog MPs only: Factor to smooth out measurement variations | _mp.dbf: smoothing (1) |
| Ana. CompensationMP (CmpAnaMpId) | analog MPs only: Compensation Measuring Point | _mp.dbf: comppntid (22) |
| Scale Group(ScaleGrpId) | analog MPs only: Name of a Scale Group | _mp.dbf: scalegroup (3) |